咨詢電話:0512-52183533
	ZPD-1000A Type Electro-Pneumatic Valve Positioner
(2) ZPD-1000A Type Electro-Pneumatic Valve Positioner
	
	Main Specifications
| 
				 Type  | 
			
				 Input Signal (mA DC)  | 
			
				 Output Pressure (kPa)  | 
			
				 Supply Pressure (MPa)  | 
			
				 Structure of Explosion-protection  | 
		
| 
				 ZPD-1111A  | 
			
				 4~20  | 
			
				 20~100  | 
			
				 0.14  | 
			
				 Standard type Flameproof type (dⅡBT4) Intrinsic safe type (iaⅡCT5)  | 
		
| 
				 ZPD-1112A  | 
			
				 4~20  | 
			
				 40~200  | 
			
				 0.25  | 
		|
| 
				 *ZPD-1251  | 
			
				 4~20  | 
			
				 
					  | 
			
				 0.35~0.5  | 
		|
| 
				 ZPD-1121A  | 
			
				 4~12/12~20  | 
			
				 20~100  | 
			
				 0.14  | 
		|
| 
				 *ZPD-1252  | 
			
				 4~12/12~20  | 
			
				 
					  | 
			
				 0.35~0.5  | 
		|
| 
				 ZPD-01  | 
			
				 0~10  | 
			
				 20~100  | 
			
				 0.14  | 
			
				 Standard type  | 
		
| 
				 40~200  | 
			
				 0.25  | 
		|||
| 
				 ZPD-01B  | 
			
				 0~10  | 
			
				 20~100  | 
			
				 0.14  | 
			
				 Flameproof type (dⅡBT4)  | 
		
| 
				 40~200  | 
			
				 0.25  | 
		|||
| 
				 *ZPD-02  | 
			
				 0~10  | 
			
				 
					  | 
			
				 0.35~0.5  | 
			
				 Standard type  | 
		
| 
				 *ZPD-02B  | 
			
				 0~10  | 
			
				 
					  | 
			
				 0.35~0.5  | 
			
				 Flameproof type (dⅡBT4)  | 
		
	Note:* Double acting type
	
Linearity: ≤±1% (SA), ≤±1.5% (DA)
Hysteresis Error:≤1% (SA), ≤1.5% (DA)
Dead Band: ≤0.4% (SA), ≤0.6% (DA)
Air Consumption:≤1.5Nm3/h (SA)
Input Resistance:250±10Ω (4~20mA)
1000±30Ω (0~10mA)
Standard Stroke: 10~100mm (Linear Motion), 50°~90°(Rotary Motion)
Control Action: Direct Action, Reverse Action
Ambient Temp.: -25~55℃ (Standard Type); -25~40℃ (Explosion-protection Type)
Relative Humidity:5%~100%
	Insulation Resistance:≥20MΩ
Supply Press. Effect:±1% (Supply press. changes at ±10% of rated values)
	ZPD-1000A Type Electro-Pneumatic Valve Positioner